Find your region

Avire-Logo-Group

For countries not listed, see the Global site.

Note: Some products are available only in certain regions. Contact us regarding local availability.

Area of Refuge Two-Way Communication Systems

As the leading manufacturer of code-compliant Emergency Communication Systems for Rescue Assistance, we provide top-tier, easy-to-install solutions, ensuring safety without compromise, while keeping your building occupants connected and safe.

NFPA 72®

NFPA 2022
NFPA 72® 2022 Two-Way Communication Requirements

  • 24.10* Two-Way Emergency Communications Systems for Rescue Assistance:
  • Editor’s Note: For the 2022 edition of the Code, the title of this section has been revised to reflect the inclusive set of requirements covered within the section. As explained in A.24.10, types of two-way ECSs can vary but are generally members of the same system type and are often required by building and fire codes in many locations within a building. These systems are provided to allow building occupants to communicate with emergency personnel when they need assistance or rescue. These systems are grouped together because they are basically the same type of equipment that provides communications in a different location. Many of the requirements found in 24.10.1 through 24.10.14 are new for the 2022 edition and include requirements from UL 2525, Two-Way Emergency Communications Systems for Rescue Assistance.
  • 24.10.1: Systems used for area of refuge emergency communications systems, stairway communications systems, elevator landing communications systems, and occupant evacuation elevator lobby communications systems shall be listed in accordance with applicable standards, such as UL 2525, Two-Way Emergency Communications Systems for Rescue Assistance.
  • 24.10.2: Where required by the enforcing authority, governing laws, codes, or standards, any communications system specified in this section shall be installed in accordance with 24.10.2 through 24.10.14
  • 24.10.3.1: When a remote call station(s) is activated by a building occupant(s), a two-way live voice communication shall be required to operate between the remote call station(s) and a constantly attended location.
  • 24.10.3.2*: The master control station shall be installed in a central control point within the building.
  • 24.10.3.3*: The constantly attended location shall be located either within the building or at a monitoring location and be approved by the authority having jurisdiction.
  • 24.10.6*: If the central control point is not constantly attended, the system shall have a timed automatic communications capability to connect with an off-premises constantly attended monitoring location approved by the authority having jurisdiction, where trained personnel can initiate the appropriate response.
  • 24.10.7*: In the event of an off-premises connection, a signal shall be transmitted to the off-premises monitoring location, identifying the specific building prior to initiating the live voice two-way communication.
  • 24.10.8: Two-way emergency communications systems shall have the capability of transmitting a verbal signal to identify the specific building address to off-premises monitoring personnel before operators complete the connection to the remote call station.
  • 24.10.9*: The physical locations of the remote call stations and the master control station shall be as designated by the building code in force and the system designer and approved by the authority having jurisdiction.
  • 24.10.10: The specific location of each active remote call station shall be identified on the master control station display on a floor and area basis in accordance with 24.10.11.
  • 24.10.11: Where all active calls are not simultaneously displayed, the master control stations shall provide the following:
    • 1.) Previously answered calls shall be capable of being prioritized as urgent on the master control station to differentiate more urgent life safety related calls from less urgent calls.
    • 2.) A minimum of 8 active call station identifiers shall be visible in the following order of priority:
      • a) Previously unanswered calls, oldest first
      • b) Previously answered calls, prioritized as urgent, oldest first
      • c) Previously answered calls, not prioritized as urgent, oldest first
  • 24.10.12: The remote call stations shall provide for hands-free, two-way communication and provide an audible and a visual signal to indicate communication has occurred.

NFPA 72 2022 Supervision & Battery Backup Requirements

  • 24.10.5 All pathways between the remote call stations and the master control station shall be monitored for integrity.
  • 10.6.9 Monitoring Integrity of Power Supplies
    • 10.6.9.1 Unless otherwise permitted or required by 10.6.9.1.3 and 10.6.9.1.6, all primary and secondary power supplies shall be monitored for the presence of voltage at the point of connection to the system.
  • 24.10.14. 24.10.2.1: The secondary power supply for two-way emergency communications systems shall be capable of operating the system under quiescent load for a minimum of 24 hours and then subsequently during a fire or other emergency condition for a period of 4 hours with all remote call stations activated and all master control stations annunciating the calls.
  • 24.10.2.2: The communications system shall be capable of monitoring additional power supplies for communications equipment vital to the transmission of off-premises signals. 24.10.3*: The communications system shall comprise remotely located communications stations (remote call stations), a master control station, and a primary and secondary power supply as required by Section 10.6.

NFPA 72 2022 Signage Requirements

  • 24.10.13 Signage.
  • 24.10.13.1: Directions for the use of the two-way communications system, instructions for summoning assistance via the two-way communications system, and written identification, including in braille, of the location shall be posted adjacent to the two-way communications system.
  • 24.10.13.2: Signage shall comply with ICC/ANSI A117.1, Accessible and Usable Buildings and Facilities, requirements for visual characters.
  • 24.10.14*: The two-way communications systems specified in this section, as intended for different types of locations, shall be permitted to be integrated with each other or other emergency communications systems provided they are installed in accordance with Section 24.10.

NFPA 72 2022 Survivability Requirements

  • Editor’s Note: The 2022 edition of the Code provides new survivability requirements for area of refuge two-way ECSs. The requirements of 24.3.14.4.3 through 24.3.14.4.6.4 provide pathway survivability guidance depending on the fire resistance of a building. Installation requirements for Class N and Class X, where used, are also spelled out. When these systems are installed for use by occupants staying in the area of refuge during a fire emergency, it is important that the circuits remain survivable for at least the same time as the fire rating of the building construction.
  • 24.3.14.10: Elevator landing two-way emergency communications systems installation of all circuit pathways between all elevator lobbies and other room(s) or rated enclosure(s) containing related control equipment required for occupant communications shall comply with the requirements of 24.3.14.4.3 through 24.3.14.4.6.4.
  • 24.3.14.4.3*: Where the building is constructed with a fire resistance rating that is equal to or greater than 2 hours, the installation shall comply with 24.3.14.4.6 or provide a pathway survivability of Level 2 or Level 3.
  • 24.3.14.4.4*: Where the building is constructed with a fire resistance rating that is at least 1 hour and less than 2 hours, the installation shall comply with 24.3.14.4.6 or provide a pathway survivability of Level 4.
  • Editor’s Note:The 2022 edition of the Code provides new survivability requirements for elevator landing two-way ECSs. The requirements of 24.3.14.4.3 through 24.3.14.4.6.4 provide pathway survivability guidance depending on the fire resistance of the building. Installation requirements for Class N and Class X, where used, are also spelled out.
  • 24.3.14.11: Elevator landing two-way emergency communications systems circuits intended to transmit off-premises shall have a pathway survivability of Level 0, Level 1, Level 2, Level 3, or Level 4.
  • 24.3.14.12: Occupant evacuation elevator lobby two-way wired emergency communications systems installation of communication and control circuit pathways shall have a pathway survivability of Level 3.
  • Editor’s Note: New language affecting OEE lobby two-way wired ECSs has been added to the 2022 edition of the Code. In acknowledgement of the importance of these systems, the Code requires that a Level 3 (see 12.4.4) pathway survivability be provided for circuits for these systems.
  • 24.10.4: The remote call stations and the master control station shall communicate with each other via pathways based on their performance capabilities under abnormal (fault) conditions in accordance with the requirements for Class A, Class B, Class N, or Class X pathways specified in Chapter 12. An area of refuge has a temporary use during egress and generally serves as a staging area that provides relative safety to its occupants while potential emergencies are assessed, decisions are made, and mitigating activities are begun. NFPA 101 recognizes any floor in a building protected throughout by an approved, supervised automatic sprinkler system as an area of refuge. Circuits connecting the area of refuge communications system to the fire command center must be designed to withstand the attack of ire during the time that the occupants await assistance. Refer to the requirements of 24.3.14.9. If loudspeakers are required where remote area of refuge stations are located, the loudspeakers should be arranged so that their sound pressure levels do not inhibit the effective use of the area of refuge stations.

NFPA 72 2022 Training Requirements

  • 24.10.15* Training for Two-Way Communications Systems.
  • Editor’s Note:The 2022 edition of the Code requires that the operators of two-way communications systems master control stations be trained on the equipment and, when necessary, qualified to use the equipment. The emergency users of the remote call stations would ordinarily not receive instructions on this equipment. If there are people in a building who could possibly benefit from knowing how to operate the remote call station, nothing should prevent the individuals from receiving training on how to use the equipment


NFPA 2016 NFPA 72 2016 Two-Way Communication Requirements

  • 24.10 – Area of Refuge (Area of Rescue Assistance) Emergency Communications Systems
  • 24.10.1 Where required by the building code in force, an area of rescue assistance two-way communications system shall be installed in accordance with 24.10
  • 24.10.2 The area of Refuge (Rescue Assistance) emergency communications system shall be comprised of remotely located area of refuge stations and a central control point.
  • 24.10.5 – If the Central control point is not constantly attended, it shall have a timed automatic communications capability to connect with a constantly attended monitoring location acceptable to the authority having jurisdiction where responsible personnel can initiate the appropriate response.
  • 24.10.6 – The physical location of the central control point shall be as designated by the building code in force or the authority having jurisdiction.
  • 24.10.8 – Instructions for the use of the two-way communications system, instructions for summoning assistance via the two-way communications system, and written identifications, including in braille, of the location shall be posted adjacent to the two-way communication system.

NFPA 72 2016 Supervision Requirements

  • 24.10.4 – All pathways between a remote area of refuge station and the central control point shall be monitored for integrity.
  • 24.13.4.1 – All control units shall meet the power supply requirements of section 10.6
  • 10.6.9 Monitoring Integrity of Power Supplies
    • 10.6.9.1 Unless otherwise permitted or required by 10.6.9.1.3 and 10.6.9.1.6, all primary and secondary power supplies shall be monitored for the presence of voltage at the point of connection to the system.
  • 10.6.7.2.1 – The secondary power supply (battery backup) shall have sufficient capacity to operate the system under quiescent load (system operating in a nonalarm condition) for a minimum of 24 hours and, at the end of that period, shall be capable of operating all alarm notification appliances used for evacuation or to direct aid to the location of an emergency for 5 minutes.

NFPA 72 2016 Cable Requirements

  • 24.3.13.9.1
    Area of Refuge emergency communications systems shall have a pathway survivability of Level 2 or Level 3.
    (Level 1 is permitted where the building is less than 2 hour fire-rated construction)
    • 12.4.3 Pathway Survivability Level 2 shall consist of one or more of the following:
    • 12.4.4 Pathway Survivability Level 3: shall consist of pathways in buildings that are fully protected by an automatic sprinkler system in accordance with NFPA 13 and one or more of the following.

NFPA 72 2016 Testing Requirements: Table 14.3.1 #25:

“Periodic testing frequency” – Annual

Reproduced with permission of NFPA from NFPA 72®, National Fire Alarm and Signaling Code®, 2022 edition. Copyright© 2021, National Fire Protection Association. For a full copy of NFPA 72®, please go to www.nfpa.org.

NFPA 72® and National Fire Alarm and Signaling Code® are registered trademarks of the National Fire Protection Association, Quincy, MA. All rights reserved.

Area of Refuge Two-Way Communication Systems

In publicly accessible buildings, during a fire alarm emergency, elevators are inaccessible. The “Area of Refuge” or “Area of Rescue Assistance” concept was established to provide a safe location for building occupants, who cannot traverse the stairs without assistance, to assemble and await help or instruction from first responders.  This designated space requires a ​two-way communication system for assisted rescue during an emergency.

An Emergency Communication System for Rescue Assistance is required, by industry standards NFPA, IBC and ADA, at each elevator or bank of elevators, on each accessible floor above/below exit discharge, so the trapped parties can call for rescue assistance.

As the leading manufacturer of code-compliant Area of Refuge Two-Way Communication Systems, we provide top-tier, easy-to-install systems, ensuring safety without compromise, while keeping your building occupants connected and safe.

Are your buildings compliant? Whether you’re a low voltage contractor, a systems integrator, or a fire inspector, we’ve got the right code compliant solution for you.

Unlike conventional two-way communication systems, the SmartCommand Addressable System uses a daisy-chained method, linking up to 32 Call Boxes together. Designed to meet NFPA 72 2002 and fully conforming to UL 2525 Standards, it’s one of the first systems on the market to have the area of refuge specified UL certification, ensuring the highest standard of safety and compliance. This innovative approach reduces wire usage and installation cost, saving time and labor. 
  • Simple Installation
  • Supervised and Programmable
  • Designed for between 1-32 Call Boxes
SmartCommand-Call-Boxes
3300 Series SmartCommand Call Boxes
Each Area of Refuge is required to have hands-free, two-way emergency communication devices (Call Boxes) located on each floor above/below the main exit floor.
The SmartCommand Call Boxes provide distressed parties a means to communicate with rescue personnel during an emergency
The system Call Boxes can be daisy chained for a quick and efficient installation
Fully Conforms to UL 2525 Standard
SmartCommand-Call-Commanders
3200 Series SmartCommand Call Commanders
Code compliant Area of Refuge Systems require a central control point where the Call Boxes call for emergency assistance.
The Call Commander (Master Station) provides a means of communication between stranded individuals, rescue personnel, and offsite parties
Fully conforms to UL 2525 Standards
3400_SmartCommand-BOSS
SmartCommand BOSS 3400
The BOSS, or the “brains” of the SmartCommand System, provides power and communication to the Call Boxes and Call Commander through 2 pair cable.
The BOSS was engineered to include built-in state of the art supervision and communication capabilities and monitored for integrity typically by the fire alarm panel
Fully conforms to UL 2525 Standards for NFPA 72 supervision requirements
1000-Power-Supply_2
UPS Power Supply 1000
Designed to meet essential backup requirements (dictated by NFPA 72), ensuring that your system remains operational for a minimum of 24 hours under quiescent load (when the system is in a non-alarm condition).
Following this period, it retains the capability to activate all alarm notification appliances used for evacuation or directing aid to the area of refuge, functioning for 60 minutes in total darkness.
Our SmartRescue Analog-Based Two-Way Communication System is designed to provide robust two-way communication for an Area of Refuge, utilizing a home run configuration, where each call box is wired directly to the central command base station. With a legacy of reliability and widespread use in the market, these systems offer a proven solution for safety and communication.
  • Home-Run Configuration
  • Independent
  • Compatible
  • Scalable
SmartRescue-Call-Boxes
2100 Series SmartRescue Call Boxes
Each Area of Refuge requires hands-free, two-way emergency communication devices (Call Boxes) on each floor above and below the main exit floor.
The SmartRescue Call Boxes, utilizing an analog home run configuration, offer an efficient means for distressed individuals to communicate with rescue personnel during an emergency
Equipped with built-in battery backup, these Call Boxes ensure uninterrupted communication even during power failures
SmartRescue-BaseStations
2500 Series SmartRescue Base Stations
A code-compliant Area of Refuge System requires a central control point to manage emergency assistance calls from Call Boxes.
The SmartRescue Base Stations, utilizing an analog home run configuration, provide a seamless means of communication between stranded individuals, rescue personnel, and offsite parties
Equipped with built-in battery backup, these base stations ensure uninterrupted communication even during power failures
Designed for smaller installations of up to 10 Call Boxes, the SmartRescue Base Stations provide an affordable yet robust solution without compromising on quality or compliance
SmartRescue-Power-Supplies
2500-PWR24U Power Supply
The 2500-PWR24AL provides 24vdc power to the RATH Area of Refuge call boxes while meeting backup requirements as dictated by NFPA 72.
The power supply ensures that your system remains operational for a minimum of 24 hours under quiescent load (when the system is in a non-alarm condition)
SmartRescue-360-Supervision
SmartRescue 360° Supervision
NFPA 72 2016 Supervision requirements state that pathways between the remote call stations and the master control station shall be monitored for integrity. To meet these requirements:
Each 2100 Series Call Box comes with built-in communication verification software and a failure relay output which can be connected to an addressable fire alarm module or the fire control panel
Power Supervision requires an additional purchase of the 2500-PWR24U power supply
The Command Center Two-Way Emergency Communication System is designed to provide efficient two-way, person-to-person voice communication for Area of Refuge, accommodating an impressive range of 1 to 116 Call Boxes. Utilizing a home run configuration with only one pair of wires needed between each Call Box and the head end. All components are crafted to meet current industry codes, ensuring top-tier reliability and compliance.
  • Home-Run Configuration
  • Independent
  • Compatible
  • Scalable
Command-Center-Call-Boxes
2400 Series Command Center Call Boxes
Each Area of Refuge requires hands-free, two-way emergency communication devices (Call Boxes) on each floor above and below the main exit floor.
The Command Center Call Boxes, designed for large-scale installations of up to 116 Call Boxes, provide a reliable means for distressed individuals to communicate with rescue personnel during an emergency
Utilizing a single pair of wires for each Call Box, the system ensures an efficient and cost-effective installation process
The Command Center Call Boxes offer a scalable and robust solution without compromising on quality or compliance, ensuring top-tier reliability and adherence to industry standards
Command-Center-Base-Stations
2500 Series Command Center and Distribution Modules
A code-compliant Area of Refuge System requires a central control point to manage emergency assistance calls from Call Boxes.
The Command Center base stations, designed to handle up to 116 Call Boxes, provide a seamless means of communication between stranded individuals, rescue personnel, and offsite parties
Utilizing an analog home run configuration with a single pair of wires for each Call Box, the system ensures an efficient and cost-effective installation process
The system includes Base Stations and Distribution Modules, Power Supply with battery backup sold separately
Command-Center-Power-Supplies
Command Center Power Supplies
Our range of power supplies for the Command Center system is designed to meet backup requirements as dictated by NFPA 72.
These power supplies ensure that your system remains operational for a minimum of 24 hours under quiescent load (when the system is in a non-alarm condition)
Following this period, they retain the capability to activate all alarm notification appliances used for evacuation or directing aid to the area of refuge, functioning for 60 minutes in total darkness
Tailored to support the Command Center’s analog configuration for up to 116 Call Boxes, these power supplies provide a robust and reliable solution, enhancing the safety and efficiency of your Area of Refuge system
Command-Center-Supervision
Command Center 360° Supervision
NFPA 72 2016 360° Supervision requirements state that pathways between the remote call stations and the master control station shall be monitored for integrity. To meet these requirements:
Each 2400 Series Call Box, Command Center, and outside phone line connect directly into the RATH Supervisor Board (2500__-SPRVSR). The 2500-__SPRVSR has a Communications Failure relay output that can be connected to an addressable fire alarm module or fire control panel
If power supervision is needed, an additional purchase of the UPS Monitor (2500-UPSMONITOR), which includes a Power Failure relay output, is required.
The IP Command Center Two-Way Communication System is more than just a communication tool; it’s a comprehensive solution that integrates with your existing network. Designed to handle between 1-128 Call Boxes, it leverages Voice Over Internet Protocol (VOIP) to provide seamless two-way communication.
  • Scalability
  • Cost-Effective
  • Remote Management
IP-Command-Center-Call-Boxes
IP Command Center Call Boxes
Each Area of Refuge requires hands-free, two-way emergency communication devices (Call Boxes) on each floor above/below the main exit floor.
The IP Command Center Call Boxes, designed to handle up to 128 Call Boxes, provide a seamless means of communication between stranded individuals, rescue personnel, and offsite parties
Utilizing Voice Over Internet Protocol (VOIP), these Call Boxes offer a clear connection over a network or internet, ensuring efficient communication
Command-Center-Base-Stations
2500 Series IP Command Center and Distribution Modules
A code-compliant Area of Refuge System requires a central control point to manage emergency assistance calls from Call Boxes.
The IP Command Center base stations, designed to handle up to 128 Call Boxes, provide a seamless means of communication between stranded individuals, rescue personnel, and offsite parties
Utilizing Voice Over Internet Protocol (VOIP), this system offers clear and efficient communication over a network or internet connection
Versatile solution that can be installed in new construction, retrofit projects, or when the building owner has upgraded their phone system to IP
The system includes Base Stations & Distribution Modules, with Power Supply and battery backup sold separately, providing a complete and robust solution for your Area of Refuge needs
This IP solution is ideal for single or multiple phone installations requiring internal communication with the Area of Refuge Call Boxes, ensuring safety and compliance without compromise
IP-Command-Center-Power-Supplies
RP7700104 UPS Power Supply
Designed to meet essential backup requirements (dictated by NFPA 72), ensuring that your system remains operational for a minimum of 24 hours under quiescent load (when the system is in a non-alarm condition).
Following this period, it retains the capability to activate all alarm notification appliances used for evacuation or directing aid to the area of refuge, functioning for 60 minutes in total darkness
IP-Command-Center-360-Supervision
IP Command Center 360° Supervision
NFPA 72 2016 Supervision requirements state that pathways between the remote call stations and the master control station shall be monitored for integrity. To meet these requirements:
Each 2400 Series Call Box, Command Center, and outside phone line connect directly into the RATH Supervisor Board (2500__-SPRVSR). The 2500-__SPRVSR has a Communications Failure relay output that can be connected to an addressable fire alarm module or fire control panel.
Each IP Call Box, along with the Command Center, has a unique IP address that the 2500-VOIPM “pings” every 10 minutes to ensure connection. If power supervision is needed, an additional purchase of the UPS Monitor (2500-UPSMONITOR), which includes a Power Failure relay output, is required.
Emergency Communication Systems for Rescue Assistance require system pathway survivability requirements that all circuits remain survivable for at least the same time as the fire rating building requirements.
  • Our cable solutions provide a dependable connection between two electronic devices, ensuring seamless communication
  • To meet the required 2-hour rating for pathway survivability, you can opt for either 2-hour fire-rated conduit or 2-hour fire-rated cable
  • 2 or 4 pair options, our communication cable offers flexibility to suit your needs
2-hour-Fire-Rated-Cable
2 Hour Fire-Rated Cable Series
Fire-resistive or fire-rated cable is designed to support Life and Fire Safety, offering “survivability” for 2 hours in harsh environments. The cable will continue to operate in high temperatures and remain fully operational for safe evacuation of building occupants. Choose from Single, 2 or 4 pair.
RP7500094-Cable
RP7500094 Communication Cable
2 Pair, 22 AWG Solid Shielded
RP7500097Communication-Cable
RP7500097 Communication Cable
4 Pair, 24 AWG, 8 Conductor
RP7500094B-Communication-Cable
RP7500094B Communication Cable
2 Pair, 18 AWG 4 Conductor Bare Copper Plenum
Comprehensive communication and evacuation plans are critical in emergency situations. Emergency Communication System for Rescue Assistance code requirements state 4 types proper signage must be visible to direct individuals to these safe locations.
  • Directions for Call Box Use
  • Illuminated
  • Door 
  • Directional 
Call-Box-Directions-for-Use-Sign
Directions for Call Box Sign
Each Call Box REQUIRES a “Directions for Call Box Use” sign to be mounted next to the Call Box in all Elevator Landings and Area(s) of Refuge/Rescue per IBC Section 1007.11 & 1009.11.
Illuminated-Signs
Illuminated Signs
Illuminated signs REQUIRED (per IBC Section 1007.9 & 1009.9)
Elevator Landing REQUIRES an illuminated sign stating “Emergency Communication” to be located by or on each wall providing access to the Elevator Landing.
Area of Refuge/Area of Rescue Assistance REQUIRES an illuminated sign stating “Area of Refuge” to be located by or on each door providing access to the Area of Refuge
Choose from Photoluminescent or Illuminated Wall Signs
Emergency-Communication-Door-Signs
Door Signs
Tactile (Braille) signage is REQUIRED at each door to an Area of Refuge, an Elevator Landing or exterior Area for Assisted Rescue complying with IBC 1007.9, IBC 1009.9 and ICC A117.1.
Direction-Sign
Directional Signs
Directional signs REQUIRED (per IBC Section 1007.10 & 1009.10) that indicate the location of the other means of egress and which are accessible means of egress shall be provided:
At exits serving a required accessible space but not providing an approved means of egress
At Elevator Landings (signs state Emergency Communication)
Within Area(s) of Refuge

Education, Training and Support

We believe that ongoing education is paramount to your professional development.

As the code and training experts, our website offers all the documentation and educational resources needed to assist you in making the right decisions.

webinar-on-computer
techTraining
Certified System Training Webinars
On demand Technical Training Webinars offer a convenient platform to educate your team on our products. Choose from Analog or IP communication systems
Lunch and Learn In Person
Lunch & Learn
Lunch & Learn Program
AIA Certified Area of Refuge Lunch & Learn program features scope and design, communication and code requirements. Available in person or remote.
Specifiers corner architect
Specifiers’ Corner
Designed to provide essential information that may be needed for a project: Submittal Documents, Manuals/Wiring Diagrams, Data Sheets and Code Requirements.